Missing command or open solenoid coil

The intended pilot command does not reach or actuate the solenoid.

What happens

The intended pilot command does not reach or actuate the solenoid.

Typical symptoms

Heat pump stays in the wrong mode even though the compressor runs.

Checks that distinguish this cause

Identify expected O/B logic and current mode, then verify the command across the actual coil terminals. Separate thermostat setup, cable, board output and isolated coil tests.

What can look similar

A main valve can stick even with a valid electrical command. Defrost may intentionally change the command.

Repair direction

Repair the proven command path or replace the approved failed solenoid.

Verify the repair

Verify heating, cooling and the documented defrost behavior.

Equipment-specific limits

Electrical command does not prove the main valve shifted. O/B energization depends on the system design, and some conditions are normal during defrost.

Practice this diagnosis