Branch breaker and protection sizing · CAUSE ARTICLE

Ground fault or excessive current

A wire or load fault, locked motor or other abnormal demand makes protection operate.

What happens

A wire or load fault, locked motor or other abnormal demand makes protection operate.

Typical symptoms

Immediate trip or a trip after an unsuccessful motor start.

Checks that distinguish this cause

Stop repeated resetting. Isolate damaged equipment and separate supply, wiring and load causes using the OEM test procedure; a grounded compressor is one possibility, not the only one.

What can look similar

Improper protection sizing or excessive connection heat may trip a circuit without a grounded motor.

Repair direction

Repair the verified cause before restoring operation. Never increase the protection rating to suppress trips.

Verify the repair

Verify circuit integrity and operating current against the approved design.

Equipment-specific limits

Use the nameplate maximum overcurrent protection, minimum circuit ampacity and installation instructions together. Breaker size is not selected from a single running-current reading.

Practice this diagnosis

This cause is a reference topic; it does not yet have a dedicated simulated call. Browse the practice board.

References and applicability

Original HVACSim explanations with manufacturer and instrument-maker references for further reading. These resources support the subject; their model-specific examples are not specifications for every system.

Editorial review: 2026-09-29. Verify the current manual for the installed model.