What happens
An obstruction, incorrect fall or unintended rise prevents water from leaving the indoor pan.
Typical symptoms
Indoor dripping during cooling, pan backup or leakage soon after installation.
Checks that distinguish this cause
Inspect the drain route, mounting level and outlet against the indoor unit manual. Perform its specified drain test; check whether accumulated ice is melting into the pan.
What can look similar
Condensation on exposed piping can drip outside a correctly draining pan.
Repair direction
Clear the verified obstruction and restore the permitted routing and cabinet mounting.
Verify the repair
Verify drainage under the prescribed test and a sustained cooling cycle without leakage.
Equipment-specific limits
Drain lift, hose routing, traps, vents and overflow wiring differ by indoor style and pump. Do not bypass overflow protection or assume a high-wall drain design suits a cassette.