Appearance
Disconnect and line fuses · CAUSE ARTICLE

Open line fuse or lost supply leg

A fuse or upstream interruption removes one or more intended supply conductors.

What happens

A fuse or upstream interruption removes one or more intended supply conductors.

Typical symptoms

Outdoor unit will not start even though the breaker handle appears on.

Checks that distinguish this cause

A qualified technician checks the intended line-to-line supply and each required conductor along the diagram. Test removed fuses only after safe isolation and investigate why a fuse opened.

What can look similar

Backfeed through motors can make a lost leg appear energized. Leg-to-ground readings alone do not establish a complete supply.

Repair direction

Correct the proven supply fault and use the specified fuse type and rating.

Verify the repair

Confirm the complete supply under load and no repeat protective operation.

Equipment-specific limits

The line side can remain energized with the pullout removed. A non-fused disconnect has no fuse to test.